Mar 19, 2018

Core saturation of transformer

Core saturation


Transformers are also constrained in their performance by the magnetic flux limitations of the core. For ferromagnetic core transformers, we must be mindful of the saturation limits of the core. Remember that ferromagnetic materials cannot support infinite magnetic flux densities: they tend to "saturate" at a certain level (dictated by the material and core dimensions), meaning that further increases in magnetic field force (mmf) do not result in proportional increases in magnetic field flux (Φ).

Feb 20, 2018

Three-Phase Transformer Circuits

Three-Phase Transformer Circuits

Since three-phase is used so often for power distribution systems, it makes sense that we would need three-phase transformers to be able to step voltages up or down. This is only partially true, as regular single-phase transformers can be ganged together to transform power between two three-phase systems in a variety of configurations, eliminating the requirement for a special three-phase transformer. However, special three-phase transformers are built for those tasks, and are able to perform with less material requirement, less size, and less weight from their modular counterparts.

Feb 7, 2018

Energy losses in Transformer

Transformer Energy losses


When transformers transfer power, they do so with a minimum of loss. As it was stated earlier, modern power transformer designs typically exceed 95% efficiency. It is good to know where some of this lost power goes, however, and what causes it to be lost.

Jan 28, 2018

Instruments transformers and its applications

Special transformers and applications
Because transformers can step voltage and current to different levels, and because power is transferred equivalently between primary and secondary windings, they can be used to "convert" the impedance of a load to a different level. That last phrase deserves some explanation, so let's investigate what it means.

Transformer Winding configurations

Winding configurations

Transformers are very versatile devices. The basic concept of energy transfer between mutual inductors is useful enough between a single primary and single secondary coil, but transformers don't have to be made with just two sets of windings. Consider this transformer circuit:

Jan 24, 2018

Step-up and step-down transformers

 Transformers

So far, we've observed simulations of transformers where the primary and secondary winding were of identical inductance, giving approximately equal voltage and current levels in both circuits. Equality of voltage and current between the primary and secondary sides of a transformer, however, is not the norm for all transformers. If the inductance of the two winding are not equal, something interesting happens

Jan 21, 2018

Vector Group of Transformer

Introduction:

Three phase transformer consists of three sets of primary windings, one for each phase, and three sets of secondary windings wound on the same iron core. Separate single-phase transformers can be used and externally interconnected to yield the same results as a 3-phase unit.

Parallel Operation of Transformers

§  For supplying a load in excess of the rating of an existing transformer, two or more transformers may be connected in parallel with the existing transformer. The transformers are connected in parallel when load on one of the transformers is more than its capacity. The reliability is increased with parallel operation than to have single larger unit. The cost associated with maintaining the spares is less when two transformers are connected in parallel.

Jan 18, 2018

Transformer-Mutual inductance and basic operation

Mutual inductance and basic operation

Suppose we were to wrap a coil of insulated wire around a loop of ferromagnetic material and energize this coil with an AC voltage source:
As an inductor, we would expect this iron-core coil to oppose the applied voltage with its

Jan 6, 2018

Abstract of National Electrical Code for Transformer’s Protection

  • According to NEC 450.4, “each transformer 600 volts, nominal, or less shall be protected by an individual over current device installed in series with each ungrounded input conductor.
  • Such over current device shall be rated or set at not more than 125% of the rated full-load input current of the auto transformer.